Short-Term to 50-Year Design Strength Reality Check

Enter any supplier’s published crush figure and watch it collapse once creep (long-term behaviour) and the CIRIA C737:2016 partial material factor are applied. This is an illustrative calculator for comparing catalogue claims — not a Storm Manage design value.

Inputs

Step 1

Catalogue tonnages are short-term crush figures, not design values.

Step 2

From a long-term BS EN 17151 programme; competing BBA-certified crates publish 121.2 and 137.5 kN/m².

Step 3

Values published in BBA certificates for competing PP crates, applied per CIRIA C737:2016.

Result

Design strength Pd
kN/m²
Reduction from catalogue
Of catalogue figure retained
%
Characteristic / γm
Short-term (catalogue)
50-yr characteristic
50-yr design Pd

Worked reference rows

Published figures for competing BBA-certified PP crates (brands withheld) alongside Storm Manage’s honest position.

Crate Short-term (kN/m²) 50-yr characteristic (kN/m²) 50-yr design Pd (kN/m²) γm
Competing Crate A 363.0 121.2 72.4 1.67
Competing Crate B 438.8 137.5 76.0 1.81
Storm Manage SG-H60 600 † not yet independently derived not published

† 600 kN/m² was recorded without specimen failure over a 0.5 m² face (Intertek, third-party, ISO/IEC 17025 process, Report 190702149GZU-001). This is a short-term lower bound because the 300 kN loading cell reached capacity, not the module. Storm Manage holds no independently derived 50-year design strength; a 60-ton creep test record is released on request.